English

K3163i Intelligent Protection Relay Test Set

Item No.: 201102
All-in-One design, weight < 17.5kg;
High Power & Accuracy with 6x35A & 4x310V analog outputs;
Complying IEC61850 Sampling Value & GOOSE;
The ever-expanding test library templates;
Optional advance functions like energy meter and transducer calibration etc.
Description Specifications Advanced Ordering instructions
Basic Functions
Universal Relay Test Applications
10 Channels (6x35A & 4x310V) outputs, Each output channels are independent and simultaneous control of magnitude, Phase angle and frequency values, able to inject DC, AC sine wave and up to 60x harmonics.
13 Low-level channels outputs up to 8Vac/10Vdc max.
100/1000Mbit Fiber port for SMV and GOOSE simulations
Variable battery simulator, DC 0-350V, 140Watts max.
Transient play back up to 3KHz
Fully function KRT software testing modules
Graphical test modules and templates for testing of various relays
Quick relay testing facility in Manual mode
Shot/Search/Check, Point & Click testing
RIO/XRIO import & export facility
Switch on to fault test(SOTF)
Power system model for dynamic testing
Online Vector display
Automatic test results assume
Automatic test report creation
Inbuilt GPS and IRIG-B sync end-to-end testing
Anti-clipping detect, Wrong wiring connect alarm and self-protect, overload and overheat protection
3-Years guarantee of free repair and life-long maintenance
Lightweight, <18Kg
Free software upgrade
 

Advance Feature
Complied IEC61850-9-1, IEC61850-9-2, IEC60044-7/8, etc
Transducer calibration (0.02 class)
Energy meter calibration (Mechanical & Electronic meters)

 
Type of relays can be tested:
Items ANSI® No.
IEC61850 numerical IEDs relay & merge unit  
Distance protection relay 21
Synchronising or synchronism-check relays 25
Undervoltage relays 27
Directional Power relays 32
Undercurrent or underpower relays 37
Negative sequence overcurrent relays 46
Overcurrent/ground fault relays 50
Inverse time overcurrent/ground fault relays 51
Power factor relays 55
Overvoltage relays 59
Voltage or current balance relays 60
Directional overcurrent relays 67
Directional ground fault relays 67N
DC overcurrent relays 76
Phase-angle measuring or out-of-step protection relays 78
Automatic reclosing devices 79
Frequency relays 81
Motor overload protection relays 86
Differential protection relays 87
Directional voltage relays 91
Voltage and power directional relays 92
Tripping relays 94
Voltage regulating relays  
Overimpedance relays, Z>  
Underimpedance relays, Z  
Time-delay relays  
Voltage Outputs
Output Range & Power 4×310 V ac (L-N) 124 VA max each
3×350 V dc (L-N) 140 W max each
Accuracy <0.02%Rd+0.005Rg Typ.
<0.05%Rd+0.01Rg Guar.
±10mV @ <5V dc
±0.5% @ ≥5V dc
Voltage Range Range I : 30V
Range II : 310V
Automatic Range
DC Offset <20mV Typ./ <100mV Guar
Resolution 1mV
Distortion <0.015%Typ. / <0.05% Guar.
Current Outputs
Output Range & Power 6×35A ac (L-N) 480 VA max each
70A ac (2L-N) 850 VA max each
1×100A ac (6L-N) 1200 VA max
3×20A dc (L-N) 300W max each
Accuracy <0.03%Rd+0.02Rg Typ. 
<0.1%Rd+0.05Rg Guar.
±5mA @ <1A dc
±0.5% @ ≥1A dc
Current Range Range I: 3A
Range II: 35A
Automatic Range
DC Offset <3mA Typ./ <10mA Guar
Resolution 1mA
Distortion <0.025%Typ. / <0.07% Guar.
Low-Level Output
Quantity 13 Channels, 16 pin combination female socket
Voltage Outputs Range AC 0~8V, DC 0~10V
Current Outputs Range Nominal 2mA, 10mA max transient
Output Power ≥0.5VA
Accuracy (0.01~0.8 Vrms):<0.05% Typ. / <0.1% Guar.
(0.8~8 Vrms): <0.02% Typ. / <0.05% Guar.
Resolution 0.25mV
Distortion (THD%) <0.05% Typ. / <0.1% Guar.
Frequency Range 0~3000KHz
DC Offset <0.15mV Typ. / <1.5mV Guar.
Frequency & Phase Angle
Frequency Range DC~1KHz, 3KHz transient
Frequency Accuracy ±0.5ppm
Frequency Resolution 0.001 Hz
Phase Range -360°~360°
Phase Accuracy <0.02° Typ. / <0.1° Guar. 50/60Hz
Phase Resolution 0.001°
Aux. DC Voltage Source (Battery simulator)
Range 0~350V @ 140W max
Accuracy 0.5%Rg Guar.
Binary Input
Quantity 8pairs
Type wet/dry, measurement
Threshold 10~600Vdc or potential free, Programmable
Time resolution 10us
Sampling Rate 10KHz
Debounce time 0~25ms (Software Controlled)
Time range Infinite
Time errors ±1ms @ 1s, ±0.1% @ >1s
Galvanic isolation 4 isolated with each 2 pairs
Binary Output (Relay Type)
Quantity 4pairs
Type Potential free relay contacts, software controlled
Break Capacity AC Vmax: 400Vac / Imax:8A / Pmax:2500VA
Break Capacity DC Vmax: 300Vdc / Imax:5A / Pmax:150W
Binary Output (Semiconductor Type)
Quantity 4pairs
Type: Open-collector, Combination type female
Break Capacity DC 5~15Vdc / 5mA, 10mA max
AC not permit
Response time: 100us
Synchronization
Synchronization Mode  GPS, SMA type antenna connector
IRIG-B (Optical fiber, FT3 type)
Power supply & Environment
Nominal Input Voltage 100~240Vac
Permissible Input Voltage 85~260Vac, 125~350VDC
Nominal Frequency 50/60Hz
Permissible Frequency 45Hz~65Hz
Power Consumption 1500 VA max
Connection Type Standard AC socket 60320
Operating Temperature -10℃~55℃
Storage Temperature -20℃~70℃
Humidity <95%RH, non-condensing
Others
PC Connection RJ45 Ethernet, 10/100M
Grounding Terminal 4mm banana socket
Weight 17.5 Kg
Dimensions(W x D x H) 468×375×164(mm) 
 
(Optional Modules)
 
IEC61850 functions:  
Fully complying IEC61850 Sampling value and GOOSE; (IEC61850-9-1, IEC61850-9-2/(LE), IEC60044-7/8)
Able to simultaneously output sampling value and analog signals, or subscriber and publish GOOSE message and relay contact binary I/O function.
Up to 36 sampling value channels can be mapped.
IEC61850 Fiber & GOOSE Ethernet Ports (Optional Function)
Fiber Ports 2 x 100Base-FX Full Duplex, LC type
(Optional to 10/100Mbit, Ethernet RJ45 type)
Fiber Type 62.5/125um (Multiple optical fiber, Orange Red)
Wavelength 1310nm
Transmit Distance >1Km
Indicator Spd Green(light): Valid connection
Link/Act Yellow(Blinking): Data exchanging
Note: Hardware is ready, to be active
 
Transducer Calibration Function:
DC Measurement Input  Hardware is ready, to be active
Voltage Input Range 0~±10V dc
Max Input ±11V dc
Accuracy <0.2% rg Typ. <0.5% rg Guar.
Input Impedance 1M ohm
Current Input Range 0~±1mA / 1~±20mA, auto range
Max Input 600mA
Accuracy <0.2% rg Typ. <0.5% rg Guar.
Input Impedance 15 ohm
 
 
Energy Meter Calibration Function:
Energy Meter Calibration Hardware is ready, to be active
Sensor Usage Mechanical meters / Electronic meters
Sensor Output High lever:>4.5V, Low level:<0.2V
Pulse Input 1 pulse input port, 5Vdc high level valid only.
Pulse Range 500KHz pulse input Max.
Pulse Output 1 Transistor output, Open-collector, 5Vdc/5mA
 
Model Current Outputs Voltage Outputs Optional
K3166i 6×35A @ 450VA max
3×70A @ 850VA max
7×310V @ 90VA max
 IEC61850 SV
● IEC61850 GOOSE
● Energy meter cal.
● Transducer cal.
K3163i 6×35A @ 450VA max
3×70A @ 850VA max
4×310V @ 124VA max
K3130i 3×35A @ 450VA max 4×310V @ 124VA max