Detailed Product Description
PMC180 three phase digital power meter
-
Complete power parameter measurement, energy measurement, 31 order voltage / current harmonic analysis.
-
Threshold Crossing Alert for power parameter, online monitoring, relay relevance alarm output.
-
Support 2 channel DI/DO, can configure transducer output.
-
Support MODBUS-RTU, RS485 communication.
Overview
PMC180 series three phase digital power meter adopts customized, modularized, high brightness LED display, very beautiful and grand; use low-power microprocessor as core, to achieve all-electric parameter measurement and energy metering. Can optional configure various binary, relay, analog output interface to achieve user’s various needs; integrates RS-485 communication ports, can easily fulfill the integration of various intelligent distribution System. The product function is practical, easy to use and maintenance. Can be used in on-site equipment monitoring and control , provide measure support for electric application experts, provide data basis for SCADA and Smart Grid, provide decision-making basis for effective intelligent energy management.
Function Features
|
Function Features
|
PMC180Z
|
PMC180C
|
PMC180P
|
PMC180U
|
PMC180I
|
|
Instantaneous real virtual value
|
|
|
|
|
|
|
current
single phase & neutral line
|
◆
|
|
◆
|
|
◆
|
|
voltage
Line/line & Phase/Line
|
◆
|
|
◆
|
◆
|
|
|
frequency
|
◆
|
|
|
|
|
|
active power
Three phase & single phase
|
◆
|
|
◆
|
|
|
|
reactive power
Three phase & single phase
|
◆
|
|
|
|
|
|
power factor
Three phase & single phase
|
◆
|
◆
|
|
|
|
|
Energy
|
|
|
|
|
|
|
active energy
|
◆
|
|
|
|
|
|
reactive energy
|
◆
|
|
|
|
|
|
Power Quality
|
|
|
|
|
|
|
Harmonic distortion
current & voltage
|
◆
|
|
|
|
|
|
31 order harmonic analysis
voltage & current
|
◆
|
|
|
|
|
|
Communication
|
|
|
|
|
|
|
RS485 /MODBUS protocol
|
◆
|
◆
|
◆
|
◆
|
◆
|
|
Display
|
|
|
|
|
|
|
LED display
|
◆
|
◆
|
◆
|
◆
|
◆
|
|
other
|
|
|
|
|
|
|
2 channel DI
|
◆
|
◆
|
◆
|
◆
|
◆
|
|
*2 channel DO
|
◆
|
◆
|
◆
|
◆
|
◆
|
|
*1 channel AO:4-20Ma
|
◆
|
◆
|
◆
|
◆
|
◆
|
|
2 channel limits alarm
|
◆
|
◆
|
◆
|
◆
|
◆
|
|
support program online upgrade
|
◆
|
◆
|
◆
|
◆
|
◆
|
Technical parameter
|
Electrical Characteristics
|
|
Measurement Type
|
Three-phase three-wire AC system
Three-phase four-wire AC system
|
|
|
Sampling rate: 64 times per cysle
|
|
Data refresh rate
|
1S
|
|
Measurement Accuracy
|
Current
|
0.2%
|
|
Voltage
|
0.2%
|
|
Power
|
0.5%
|
|
Frequency
|
0.05Hz
|
|
Active Energy
|
1.0%
|
|
Reactive Energy
|
2.0%
|
|
AO
|
1%
|
|
Input voltage characteristics
|
Measuring voltage
|
3 X 220/380V(connected directly)
|
|
3 X 57.7/100V(connected by CT)
|
|
Allowed overload
|
1.2 times / continuous
|
|
Input impedance
|
1.8MΩ
|
|
Input current characteristic
|
Measuring current
|
5A or 1A (connected by CT)
|
|
Allowed overload
|
1.2 times / continuous
|
|
Input impedance
|
<0.1Ω
|
|
Binary INPUT
|
Working voltage
|
12~24 VDC (external power supply)
|
|
Input impedance
|
12KΩ
|
|
Isolation voltage
|
2KV
|
|
Relay output
|
Node Type
|
Mechanical shock
|
|
Node capacity
|
220 VAC/5A, 30 VDC/5A
|
|
4-20mA
DC Output
|
Open circuit voltage
|
5VDC
|
|
overload capacity
|
≤200Ω
|
|
Isolation voltage
|
2KV
|
|
Working power supply
|
AC
|
85~265 VAC/45-65Hz
|
|
DC
|
100~300 VDC
|
|
Power dissipation
|
< 3W
|
|
Mechanical properties
|
|
Weight
|
0.5kg
|
|
IP protection grade
|
panel IP52, body IP30
|
|
Size
|
96 X 96 X 72 mm
|
|
Operating temperature
|
-25~70℃
|
|
Storage Temperature
|
-40~85℃
|
|
Relative Humidity
|
5% - 90%RH, No condensation
|
|
EMC
|
|
Electrostatic discharge interference
|
IEC 61000-4-2, Level 4
|
|
Group of anti-fast transient pulse
|
IEC 61000-4-4, Level 4
|
|
Anti-impact
|
IEC 61000-4-5, Level 3
|
|
Anti-frequency magnetic field
|
IEC 61000-4-8, Level 3
|
|
Electrical insulation performance
|
|
Insulation resistance
|
GB/T13729, >50MΩ
|
|
Frequency withstand voltage
|
GB/T13729, AC 2KV 50Hz /1min
|
|
Impulse voltage
|
GB/T13729, 5KV, 1.2/50us
|